skip navigation links 
 
 Search Options 
Index | Site Map | FAQ | Facility Info | Reading Rm | New | Help | Glossary | Contact Us blue spacer  
secondary page banner Return to NRC Home Page

Peach Bottom 3

2Q/2008 Performance Indicators

Licensee's General Comments: none



Link to Notes

Unplanned Scrams per 7000 Critical Hrs 3Q/06 4Q/06 1Q/07 2Q/07 3Q/07 4Q/07 1Q/08 2Q/08
Unplanned scrams 0 0 0 0 0 0 0 0
Critical hours 2208.0 2209.0 2159.0 2184.0 2038.3 1911.4 2146.9 2184.0
                 
Indicator value 0 0 0 0 0 0 0 0


Licensee Comments: none




Link to Notes

Unplanned Power Changes per 7000 Critical Hrs 3Q/06 4Q/06 1Q/07 2Q/07 3Q/07 4Q/07 1Q/08 2Q/08
Unplanned power changes 0 0 1.0 0 0 0 1.0 0
Critical hours 2208.0 2209.0 2159.0 2184.0 2038.3 1911.4 2146.9 2184.0
                 
Indicator value 0.8 0 0.8 0.8 0.8 0.8 0.8 0.8

Licensee Comments: none






Link to Notes

Unplanned Scrams with Complications 3Q/06 4Q/06 1Q/07 2Q/07 3Q/07 4Q/07 1Q/08 2Q/08
Scrams with complications   0 0 0 0 0 0 0
                 
                 
Indicator value         0.0 0.0 0.0 0.0

Licensee Comments: none






Link to Notes

Safety System Functional Failures (BWR) 3Q/06 4Q/06 1Q/07 2Q/07 3Q/07 4Q/07 1Q/08 2Q/08
Safety System Functional Failures 0 0 0 0 0 0 0 0
                 
Indicator value 0 0 0 0 0 0 0 0

Licensee Comments: none






Link to Notes

Mitigating Systems Performance Index, Emergency AC Power System 3Q/06 4Q/06 1Q/07 2Q/07 3Q/07 4Q/07 1Q/08 2Q/08
UAI (ΔCDF) 8.40E-08 9.70E-08 2.20E-07 1.60E-07 1.40E-07 1.40E-07 6.10E-08 7.90E-08
URI (ΔCDF) -8.10E-08 -1.80E-07 -1.80E-07 -9.50E-08 5.60E-08 7.20E-08 1.10E-07 -5.00E-07
PLE NO NO NO NO NO NO NO NO
                 
Indicator value 3.00E-09 -8.30E-08 4.00E-08 6.50E-08 1.96E-07 2.12E-07 1.71E-07 -4.21E-07

Licensee Comments: none






Link to Notes

Mitigating Systems Performance Index, High Pressure Injection System 3Q/06 4Q/06 1Q/07 2Q/07 3Q/07 4Q/07 1Q/08 2Q/08
UAI (ΔCDF) 1.30E-08 1.30E-08 7.00E-10 7.00E-10 9.20E-10 1.30E-09 -5.50E-09 -5.20E-09
URI (ΔCDF) 1.90E-07 1.90E-07 6.10E-08 6.10E-08 6.10E-08 6.10E-08 -7.10E-08 -7.10E-08
PLE NO NO NO NO NO NO NO NO
                 
Indicator value 2.03E-07 2.03E-07 6.17E-08 6.17E-08 6.19E-08 6.23E-08 -7.65E-08 -7.62E-08

Licensee Comments: none






Link to Notes

Mitigating Systems Performance Index, Heat Removal System 3Q/06 4Q/06 1Q/07 2Q/07 3Q/07 4Q/07 1Q/08 2Q/08
UAI (ΔCDF) -5.50E-08 -5.50E-08 -5.50E-08 -4.80E-08 -4.80E-08 -4.30E-08 -4.40E-08 -1.60E-08
URI (ΔCDF) -1.40E-07 -1.40E-07 -1.40E-07 -1.20E-07 -1.20E-07 -1.20E-07 -1.20E-07 -1.20E-07
PLE NO NO NO NO NO NO NO NO
                 
Indicator value -1.95E-07 -1.95E-07 -1.95E-07 -1.68E-07 -1.68E-07 -1.63E-07 -1.64E-07 -1.36E-07

Licensee Comments: none






Link to Notes

Mitigating Systems Performance Index, Residual Heat Removal System 3Q/06 4Q/06 1Q/07 2Q/07 3Q/07 4Q/07 1Q/08 2Q/08
UAI (ΔCDF) -8.20E-10 -3.60E-10 -3.60E-10 -1.00E-10 -1.00E-10 1.50E-10 1.50E-10 1.50E-10
URI (ΔCDF) -1.90E-09 -1.90E-09 -1.90E-09 -8.70E-10 -8.70E-10 -8.70E-10 -8.70E-10 -8.70E-10
PLE NO NO NO NO NO NO NO NO
                 
Indicator value -2.72E-09 -2.26E-09 -2.26E-09 -9.70E-10 -9.70E-10 -7.20E-10 -7.20E-10 -7.20E-10

Licensee Comments: none






Link to Notes

Mitigating Systems Performance Index, Cooling Water Systems 3Q/06 4Q/06 1Q/07 2Q/07 3Q/07 4Q/07 1Q/08 2Q/08
UAI (ΔCDF) -6.20E-10 -1.10E-09 -1.60E-10 -2.70E-10 -2.60E-10 3.40E-10 3.00E-10 3.00E-10
URI (ΔCDF) -5.50E-09 -5.50E-09 -5.50E-09 -6.60E-09 -3.50E-09 -3.50E-09 -3.50E-09 -3.50E-09
PLE NO NO NO NO NO NO NO NO
                 
Indicator value -6.12E-09 -6.60E-09 -5.66E-09 -6.87E-09 -3.76E-09 -3.16E-09 -3.20E-09 -3.20E-09

Licensee Comments: none






Link to Notes

Reactor Coolant System Activity 7/06 8/06 9/06 10/06 11/06 12/06 1/07 2/07 3/07 4/07 5/07 6/07
Maximum activity 0.000189 0.000134 0.000226 0.000203 0.000108 0.000079 0.000080 0.000092 0.000102 0.000063 0.000076 0.000060
Technical specification limit 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2
                         
Indicator value 0.1 0.1 0.1 0.1 0.1 0 0 0 0.1 0 0 0
Reactor Coolant System Activity 7/07 8/07 9/07 10/07 11/07 12/07 1/08 2/08 3/08 4/08 5/08 6/08
Maximum activity 0.000163 0.000097 0.000099 0.000264 0.000470 0.000029 0.000037 0.000070 0.000097 0.000125 0.000094 0.000149
Technical specification limit 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2
                         
Indicator value 0.1 0 0 0.1 0.2 0 0 0 0 0.1 0 0.1

Licensee Comments: none






Link to Notes

Reactor Coolant System Leakage 7/06 8/06 9/06 10/06 11/06 12/06 1/07 2/07 3/07 4/07 5/07 6/07
Maximum leakage 1.470 1.830 1.840 1.450 1.420 1.450 1.420 1.410 1.470 7.390 7.520 7.530
Technical specification limit 25.0 25.0 25.0 25.0 25.0 25.0 25.0 25.0 25.0 25.0 25.0 25.0
                         
Indicator value 5.9 7.3 7.4 5.8 5.7 5.8 5.7 5.6 5.9 29.6 30.1 30.1
Reactor Coolant System Leakage 7/07 8/07 9/07 10/07 11/07 12/07 1/08 2/08 3/08 4/08 5/08 6/08
Maximum leakage 7.530 1.680 1.660 1.570 1.570 1.540 1.540 1.540 1.640 1.650 1.660 1.680
Technical specification limit 25.0 25.0 25.0 25.0 25.0 25.0 25.0 25.0 25.0 25.0 25.0 25.0
                         
Indicator value 30.1 6.7 6.6 6.3 6.3 6.2 6.2 6.2 6.6 6.6 6.6 6.7

Licensee Comments: none






Link to Notes

Drill/Exercise Performance 3Q/06 4Q/06 1Q/07 2Q/07 3Q/07 4Q/07 1Q/08 2Q/08
Successful opportunities 27.0 24.0 145.0 28.0 34.0 24.0 59.0 82.0
Total opportunities 28.0 24.0 148.0 30.0 38.0 24.0 63.0 84.0
                 
Indicator value 96.7% 96.7% 97.3% 98.0% 97.2% 97.4% 96.6% 96.4%

Licensee Comments: none






Link to Notes

ERO Drill Participation 3Q/06 4Q/06 1Q/07 2Q/07 3Q/07 4Q/07 1Q/08 2Q/08
Participating Key personnel 81.0 82.0 84.0 79.0 84.0 85.0 75.0 75.0
Total Key personnel 81.0 82.0 84.0 79.0 86.0 85.0 75.0 75.0
                 
Indicator value 100.0% 100.0% 100.0% 100.0% 97.7% 100.0% 100.0% 100.0%

Licensee Comments: none






Link to Notes

Alert & Notification System 3Q/06 4Q/06 1Q/07 2Q/07 3Q/07 4Q/07 1Q/08 2Q/08
Successful siren-tests 1249 1257 1256 1258 1258 1261 1258 1255
Total sirens-tests 1261 1261 1261 1261 1261 1261 1261 1261
                 
Indicator value 99.4% 99.3% 99.3% 99.5% 99.7% 99.8% 99.8% 99.8%

Licensee Comments: none






Link to Notes

Occupational Exposure Control Effectiveness 3Q/06 4Q/06 1Q/07 2Q/07 3Q/07 4Q/07 1Q/08 2Q/08
High radiation area occurrences 0 0 0 0 0 0 0 0
Very high radiation area occurrences 0 0 0 0 0 0 0 0
Unintended exposure occurrences 0 0 0 0 0 0 0 0
Indicator value 0 0 0 0 0 0 0 0

Licensee Comments: none






Link to Notes

RETS/ODCM Radiological Effluent 3Q/06 4Q/06 1Q/07 2Q/07 3Q/07 4Q/07 1Q/08 2Q/08
RETS/ODCM occurrences 0 0 0 0 0 0 0 0
                 
Indicator value 0 0 0 0 0 0 0 0

Licensee Comments: none






Physical Protection information not publicly available.



 
 
 
 

Top of page    Action Matrix Summary |  Inspection Findings Summary |  PI Summary |  Reactor Oversight Process

Last Modified: August 4, 2008