Search Options | ||||
Index | Site Map | FAQ | Facility Info | Reading Rm | New | Help | Glossary | Contact Us |
Licensee's General Comments: none
Unplanned Scrams per 7000 Critical Hrs | 3Q/06 | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 |
Unplanned scrams | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Critical hours | 2208.0 | 2209.0 | 2159.0 | 871.7 | 2208.0 | 2209.0 | 2183.0 | 2184.0 |
Indicator value | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Licensee Comments: none
Unplanned Power Changes per 7000 Critical Hrs | 3Q/06 | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 |
Unplanned power changes | 0 | 0 | 0 | 0 | 1.0 | 0 | 0 | 0 |
Critical hours | 2208.0 | 2209.0 | 2159.0 | 871.7 | 2208.0 | 2209.0 | 2183.0 | 2184.0 |
Indicator value | 0 | 0 | 0 | 0 | 0.9 | 0.9 | 0.9 | 0.8 |
Licensee Comments: none
Unplanned Scrams with Complications | 3Q/06 | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 |
Scrams with complications | 0 | 0 | 0 | 0 | 0 | 0 | 0 | |
Indicator value | 0.0 | 0.0 | 0.0 | 0.0 |
Licensee Comments: none
Safety System Functional Failures (PWR) | 3Q/06 | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 |
Safety System Functional Failures | 0 | 1 | 0 | 0 | 0 | 0 | 0 | 0 |
Indicator value | 0 | 1 | 1 | 1 | 1 | 0 | 0 | 0 |
Licensee Comments: none
Mitigating Systems Performance Index, Emergency AC Power System | 3Q/06 | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 |
UAI (ΔCDF) | 1.40E-07 | 5.10E-08 | 5.20E-08 | 1.10E-07 | 1.10E-07 | 1.40E-07 | 9.00E-08 | 8.90E-08 |
URI (ΔCDF) | -5.50E-08 | 3.50E-09 | 3.50E-09 | 9.80E-09 | 9.80E-09 | 2.20E-07 | 1.60E-07 | 1.60E-07 |
PLE | NO | NO | NO | NO | NO | NO | NO | NO |
Indicator value | 8.50E-08 | 5.45E-08 | 5.55E-08 | 1.20E-07 | 1.20E-07 | 3.60E-07 | 2.50E-07 | 2.49E-07 |
Licensee Comments: none
Mitigating Systems Performance Index, High Pressure Injection System | 3Q/06 | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 |
UAI (ΔCDF) | 4.10E-08 | 2.80E-08 | 2.20E-07 | 1.10E-07 | 1.10E-07 | 4.50E-08 | 1.40E-07 | 1.10E-07 |
URI (ΔCDF) | -2.00E-07 | -1.40E-07 | -1.40E-07 | -1.10E-07 | -1.10E-07 | -1.10E-07 | -1.10E-07 | -1.10E-07 |
PLE | NO | NO | NO | NO | NO | NO | NO | NO |
Indicator value | -1.59E-07 | -1.12E-07 | 8.00E-08 | 0.00E+00 | 0.00E+00 | -6.50E-08 | 3.00E-08 | 0.00E+00 |
Licensee Comments: none
Mitigating Systems Performance Index, Heat Removal System | 3Q/06 | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 |
UAI (ΔCDF) | 2.60E-08 | 2.20E-08 | 2.20E-08 | -2.70E-09 | -3.10E-09 | -1.20E-08 | -1.20E-08 | -1.20E-08 |
URI (ΔCDF) | 1.10E-07 | 6.40E-08 | 6.40E-08 | 6.10E-08 | 6.10E-08 | -7.10E-08 | -7.10E-08 | -7.10E-08 |
PLE | NO | NO | NO | NO | NO | NO | NO | NO |
Indicator value | 1.36E-07 | 8.60E-08 | 8.60E-08 | 5.83E-08 | 5.79E-08 | -8.30E-08 | -8.30E-08 | -8.30E-08 |
Licensee Comments: none
Mitigating Systems Performance Index, Residual Heat Removal System | 3Q/06 | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 |
UAI (ΔCDF) | -3.70E-10 | -2.60E-10 | 3.20E-10 | 4.20E-10 | 3.90E-10 | 2.90E-12 | 2.20E-12 | 4.20E-11 |
URI (ΔCDF) | -5.00E-09 | -2.70E-09 | -2.70E-09 | -2.50E-09 | -2.50E-09 | -2.50E-09 | -2.50E-09 | -2.50E-09 |
PLE | NO | NO | NO | NO | NO | NO | NO | NO |
Indicator value | -5.37E-09 | -2.96E-09 | -2.38E-09 | -2.08E-09 | -2.11E-09 | -2.50E-09 | -2.50E-09 | -2.46E-09 |
Licensee Comments: none
Mitigating Systems Performance Index, Cooling Water Systems | 3Q/06 | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 |
UAI (ΔCDF) | -1.60E-07 | -1.40E-07 | -1.60E-07 | -1.40E-07 | -1.90E-07 | -1.90E-07 | -7.50E-08 | -7.20E-08 |
URI (ΔCDF) | 4.40E-08 | -6.80E-09 | -6.80E-09 | -3.10E-09 | -4.00E-09 | -4.00E-09 | -1.00E-08 | -1.00E-08 |
PLE | NO | NO | NO | NO | NO | NO | NO | NO |
Indicator value | -1.16E-07 | -1.47E-07 | -1.67E-07 | -1.43E-07 | -1.94E-07 | -1.94E-07 | -8.50E-08 | -8.20E-08 |
Licensee Comments: none
Reactor Coolant System Activity | 7/06 | 8/06 | 9/06 | 10/06 | 11/06 | 12/06 | 1/07 | 2/07 | 3/07 | 4/07 | 5/07 | 6/07 |
Maximum activity | 0.000457 | 0.000467 | 0.000475 | 0.000490 | 0.000499 | 0.000541 | 0.000525 | 0.000709 | 0.001150 | N/A | N/A | 0.000210 |
Technical specification limit | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 |
Indicator value | 0 | 0 | 0 | 0 | 0 | 0.1 | 0.1 | 0.1 | 0.1 | N/A | N/A | 0 |
Reactor Coolant System Activity | 7/07 | 8/07 | 9/07 | 10/07 | 11/07 | 12/07 | 1/08 | 2/08 | 3/08 | 4/08 | 5/08 | 6/08 |
Maximum activity | 0.000402 | 0.000358 | 0.000193 | 0.000314 | 0.000382 | 0.000290 | 0.000299 | 0.000309 | 0.000341 | 0.000356 | 0.000414 | 0.000347 |
Technical specification limit | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 |
Indicator value | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Licensee Comments: none
Reactor Coolant System Leakage | 7/06 | 8/06 | 9/06 | 10/06 | 11/06 | 12/06 | 1/07 | 2/07 | 3/07 | 4/07 | 5/07 | 6/07 |
Maximum leakage | 0.020 | 0.018 | 0.014 | 0.020 | 0.010 | 0.023 | 0.010 | 0.010 | 0.013 | 0 | 0.103 | 0.036 |
Technical specification limit | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 |
Indicator value | 0.2 | 0.2 | 0.1 | 0.2 | 0.1 | 0.2 | 0.1 | 0.1 | 0.1 | 0 | 1.0 | 0.4 |
Reactor Coolant System Leakage | 7/07 | 8/07 | 9/07 | 10/07 | 11/07 | 12/07 | 1/08 | 2/08 | 3/08 | 4/08 | 5/08 | 6/08 |
Maximum leakage | 0.050 | 0.120 | 0.020 | 0.030 | 0.045 | 0.004 | 0.030 | 0.088 | 0.024 | 0.005 | 0.030 | 0.050 |
Technical specification limit | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 |
Indicator value | 0.5 | 1.2 | 0.2 | 0.3 | 0.5 | 0 | 0.3 | 0.9 | 0.2 | 0.1 | 0.3 | 0.5 |
Licensee Comments: none
Drill/Exercise Performance | 3Q/06 | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 |
Successful opportunities | 71.0 | 78.0 | 113.0 | 38.0 | 88.0 | 2.0 | 68.0 | 48.0 |
Total opportunities | 78.0 | 80.0 | 116.0 | 39.0 | 90.0 | 2.0 | 72.0 | 51.0 |
Indicator value | 95.2% | 95.3% | 95.8% | 95.5% | 96.1% | 96.2% | 96.1% | 95.8% |
Licensee Comments: none
ERO Drill Participation | 3Q/06 | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 |
Participating Key personnel | 98.0 | 104.0 | 106.0 | 101.0 | 98.0 | 97.0 | 101.0 | 96.0 |
Total Key personnel | 99.0 | 106.0 | 107.0 | 102.0 | 99.0 | 98.0 | 101.0 | 98.0 |
Indicator value | 99.0% | 98.1% | 99.1% | 99.0% | 99.0% | 99.0% | 100.0% | 98.0% |
Licensee Comments: none
Alert & Notification System | 3Q/06 | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 |
Successful siren-tests | 630 | 629 | 719 | 627 | 714 | 719 | 629 | 719 |
Total sirens-tests | 630 | 630 | 720 | 630 | 720 | 720 | 630 | 720 |
Indicator value | 100.0% | 99.9% | 99.9% | 99.8% | 99.6% | 99.6% | 99.6% | 99.7% |
Licensee Comments: none
Occupational Exposure Control Effectiveness | 3Q/06 | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 |
High radiation area occurrences | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Very high radiation area occurrences | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Unintended exposure occurrences | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Indicator value | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Licensee Comments: none
RETS/ODCM Radiological Effluent | 3Q/06 | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 |
RETS/ODCM occurrences | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Indicator value | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Licensee Comments: none
Action Matrix Summary | Inspection Findings Summary | PI Summary | Reactor Oversight Process
Last Modified: August 4, 2008