Search Options | ||||
Index | Site Map | FAQ | Facility Info | Reading Rm | New | Help | Glossary | Contact Us |
Generic Environmental Impact Statement for License Renewal of Nuclear Plants Regarding Browns Ferry Nuclear Plant, Units 1, 2, and 3 (NUREG-1437, Supplement 21) Final ReportOn this page: Download complete document The following links on this page are to documents in Adobe Portable Document Format (PDF). See our Plugins, Viewers, and Other Tools page for more information. For successful viewing of PDF documents on our site please be sure to use the latest version of Adobe.
Publication InformationManuscript Completed: June 2005 Division of Regulatory Improvement Programs AbstractThe U.S. Nuclear Regulatory Commission (NRC or Commission) considered the environmental impacts of renewing nuclear power plant operating licenses (OLs) for a 20-year period in its Generic Environmental Impact Statement for License Renewal of Nuclear Plants (GEIS), NUREG-1437, Volumes 1 and 2, and codified the results in Title 10 of the Code of Federal Regulations (CFR) Part 51. In the GEIS (and its Addendum 1), the staff identifies 92 environmental issues and reaches generic conclusions related to environmental impacts for 69 of these issues that apply to all plants or to plants with specific design or site characteristics. Additional plant-specific review is required for the remaining 23 issues. These plant-specific reviews are to be included in a supplement to the GEIS. This supplemental environmental impact statement (SEIS) has been prepared in response to an application submitted to NRC by the Tennessee Valley Authority (TVA) to renew the OLs for Browns Ferry Nuclear Plant, Units 1, 2, and 3 (BFN) for an additional 20 years under 10 CFR Part 54. The SEIS includes the NRC staff’s analysis that considers and weighs the environmental impacts of the proposed action, the environmental impacts of alternatives to the proposed action, and mitigation measures available for reducing or avoiding adverse impacts. It also includes the staff’s recommendation regarding the proposed action. Regarding the 69 issues for which the GEIS reached generic conclusions, neither TVA nor the staff has identified information that is both new and significant for any issue that applies to BFN. In addition, the staff determined that information provided during the scoping process did not call into question the conclusions in the GEIS. Therefore, the staff concludes that the impacts of renewing the BFN OLs will not be greater than impacts identified for these issues in the GEIS. For each of these issues, the staff’s conclusion in the GEIS is that the impact is of SMALL(a) significance (except for collective offsite radiological impacts from the fuel cycle and high-level waste and spent fuel, which were not assigned a single significance level). The remaining 23 issues that apply to BFN are addressed in this SEIS. For each applicable issue, the staff concludes that the significance of the potential environmental impacts of renewal of the OLs is SMALL. The staff also concludes that additional mitigation measures are not likely to be sufficiently beneficial as to be warranted. The staff determined that information provided during the scoping process did not identify any new issue that has a significant environmental impact. The NRC staff recommends that the Commission determine that the adverse environmental impacts of license renewal for BFN are not so great that preserving the option of license renewal for energy-planning decisionmakers would be unreasonable. This recommendation is based on (1) the analysis and findings in the GEIS; (2) the Environmental Report submitted by TVA; (3) consultation and discussions with Federal, State, and local agencies; (4) the staff’s own independent review; and (5) the staff’s consideration of public comments. (a) Environmental effects are not detectable or are so minor that they will neither destabilize nor noticeably alter any important attribute of the resource. |
Privacy Policy |
Site Disclaimer |