Department of Labor Seal photos representing the workforce - digital imagery? copyright 2001 photodisc, inc.
Department of Labor Seal www.osha.gov  [skip navigational links] Search    Advanced Search | A-Z Index
Regulations (Standards - 29 CFR)
Audiometric test rooms - 1910.95 App D

Regulations (Standards - 29 CFR) - Table of Contents Regulations (Standards - 29 CFR) - Table of Contents
• Part Number: 1910
• Part Title: Occupational Safety and Health Standards
• Subpart: G
• Subpart Title: Occupational Health and Environment Control
• Standard Number: 1910.95 App D
• Title: Audiometric test rooms

This Appendix is Mandatory

Rooms used for audiometric testing shall not have background sound pressure levels exceeding those in Table D-1 when measured by equipment conforming at least to the Type 2 requirements of American National Standard Specification for Sound Level Meters, S1.4-1971 (R1976), and to the Class II requirements of American National Standard Specification for Octave, Half-Octave, and Third-Octave Band Filter Sets, S1.11-1971 (R1976).

TABLE D-1 - MAXIMUM ALLOWABLE OCTAVE-BAND SOUND PRESSURE LEVELS
           FOR AUDIOMETRIC TEST ROOMS

_______________________________________________________________
Octave-band center
frequency (Hz)...............  500   1000   2000   4000   8000
Sound pressure level (dB) ...   40     40     47     57     62
_______________________________________________________________


Next Standard (1910.95 App E) Next Standard (1910.95 App E)

Regulations (Standards - 29 CFR) - Table of Contents Regulations (Standards - 29 CFR) - Table of Contents



Back to Top Back to Top www.osha.gov www.dol.gov

Contact Us | Freedom of Information Act | Customer Survey
Privacy and Security Statement | Disclaimers
Occupational Safety & Health Administration
200 Constitution Avenue, NW
Washington, DC 20210