Protecting People and the EnvironmentUNITED STATES NUCLEAR REGULATORY COMMISSION
SSINS No.: 6835
IN 83-76
UNITED STATES
NUCLEAR REGULATORY COMMISSION
OFFICE OF INSPECTION AND ENFORCEMENT
WASHINGTON, D.C. 20555
November 2, 1983
Information Notice No. 83-76: REACTOR TRIP BREAKER MALFUNCTIONS
(UNDERVOLTAGE TRIP DEVICES ON GE TYPE
AK-2-25 BREAKERS)
Addressees:
All nuclear power reactor facilities holding an operating license (OL) or
construction permit (CP).
Purpose:
To advise licensees of malfunctions of the undervoltage trip attachments in
General Electric Type AK-2-25 breakers which are used in safety-related
systems. Although no specific action is being required by the NRC at this
time, it is expected that licensees will review the general problem
described for applicability to their facilities and take appropriate action.
Description of Circumstances:
Five malfunctions of the undervoltage (UV) trip device used on General
Electric Type AK-2-25 reactor trip breakers (RTB) occurred at the San Onofre
Nuclear Generating Station, Units 2 and 3. On October 28, 1983, with Unit 3
in Mode 3 (Hot Standby), while routine monthly surveillance was being
performed on the reactor protection system, the undervoltage armatures for
RTBs #5 and #8 were observed to be in a midposition rather than fully down
and in contact with the air gap adjusting screw (See Figure 1). The RTBs
were reset, observed to operate properly, and the undervoltage armatures
were observed to be properly positioned at that time.
On October 31, 1983, with both Units 2 and 3 in Mode 1 (Power Operation),
the positions of all the undervoltage armatures of the RTBs were visually
inspected. This inspection revealed that undervoltage armatures of RTB #4 on
Unit 2 and RTBs #5 and #8 on Unit 3 were not properly positioned. It has
been established that the Unit 3 breakers had been tripped and reset
subsequent to the October 28, 1983 event without further UV armature
position verification. These RTBs were reset, observed to operate properly
and the undervoltage armatures remained properly positioned.
Southern California Edison Company, the licensee, has indicated that these
malfunctions (i.e., the undervoltage armature in midposition rather than in
contact with the air gap adjusting screw) could result in the RTB failing to
trip within the specified criteria of the undervoltage trip device. Southern
California Edison Company's preliminary conclusion is that the undervoltage
armature can remain in a midposition as a result of interference (vertical)
8308310076
.
IN 83-76
November 2, 1983
Page 2 of 2
between the undervoltage armature and the copper shading ring around the
core of the coil (See Figure 1)
No action or written response to this notice is required; however, licensees
using AK-2 type breakers with undervoltage trip devices may find it prudent
to visually inspect each undervoltage armature to assure it is in its proper
position after each operation. If the UV armature were to be found in an
improper position, the NRC would consider the RTB to be inoperable. If you
have any questions regarding this notice, please contact the Regional
Administrator of the appropriate NRC Regional Office, or a Technical Contact
listed below.
Edward L. Jordan Director
Division of Emergency Preparedness
and Engineering Response
Office of Inspection and Enforcement
Technical Contacts: I. Villalva, IE
(301) 492-9635
J. T. Beard, NRR
(301) 492-7465
Attachment:
1. Figure 1
2. List of Recently Issued IE Information Notices
.