Search Options | ||||
Index | Site Map | FAQ | Facility Info | Reading Rm | New | Help | Glossary | Contact Us |
Licensee's General Comments: none
Unplanned Scrams per 7000 Critical Hrs | 3Q/06 | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 |
Unplanned scrams | 0 | 1.0 | 0 | 1.0 | 0 | 1.0 | 0 | 0 |
Critical hours | 2208.0 | 2184.7 | 1823.8 | 1674.4 | 2022.2 | 2062.2 | 1982.9 | 2184.0 |
Indicator value | 0 | 0.8 | 0.8 | 1.8 | 1.8 | 1.8 | 1.8 | 0.8 |
Licensee Comments: none
Unplanned Power Changes per 7000 Critical Hrs | 3Q/06 | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 |
Unplanned power changes | 0 | 0 | 1.0 | 1.0 | 0 | 0 | 0 | 0 |
Critical hours | 2208.0 | 2184.7 | 1823.8 | 1674.4 | 2022.2 | 2062.2 | 1982.9 | 2184.0 |
Indicator value | 0 | 0 | 0.8 | 1.8 | 1.8 | 1.8 | 0.9 | 0 |
Licensee Comments: none
Unplanned Scrams with Complications | 3Q/06 | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 |
Scrams with complications | 0 | 0 | 1.0 | 0 | 0 | 0 | 0 | |
Indicator value | 1.0 | 1.0 | 1.0 | 0.0 |
Licensee Comments: none
Safety System Functional Failures (PWR) | 3Q/06 | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 |
Safety System Functional Failures | 0 | 0 | 0 | 1 | 1 | 0 | 0 | 0 |
Indicator value | 0 | 0 | 0 | 1 | 2 | 2 | 2 | 1 |
Licensee Comments: none
Mitigating Systems Performance Index, Emergency AC Power System | 3Q/06 | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 |
UAI (ΔCDF) | 1.90E-08 | 1.90E-08 | 2.00E-08 | 1.90E-08 | 1.90E-08 | 2.00E-08 | 2.00E-08 | 4.60E-08 |
URI (ΔCDF) | -1.40E-07 | -1.40E-07 | 9.00E-09 | -9.50E-10 | -9.50E-10 | -9.50E-10 | -9.50E-10 | 2.10E-07 |
PLE | NO | NO | NO | NO | NO | NO | NO | NO |
Indicator value | -1.21E-07 | -1.21E-07 | 2.90E-08 | 1.81E-08 | 1.81E-08 | 1.91E-08 | 1.91E-08 | 2.56E-07 |
Licensee Comments: none
Mitigating Systems Performance Index, High Pressure Injection System | 3Q/06 | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 |
UAI (ΔCDF) | -2.10E-08 | -2.10E-08 | -2.00E-08 | -2.00E-08 | -2.00E-08 | -2.00E-08 | -2.10E-08 | -2.10E-08 |
URI (ΔCDF) | 9.20E-08 | 9.10E-08 | 9.10E-08 | 9.00E-08 | 9.00E-08 | 9.00E-08 | 8.90E-08 | 6.40E-08 |
PLE | NO | NO | NO | NO | NO | NO | NO | NO |
Indicator value | 7.10E-08 | 7.00E-08 | 7.10E-08 | 7.00E-08 | 7.00E-08 | 7.00E-08 | 6.80E-08 | 4.30E-08 |
Licensee Comments: none
Mitigating Systems Performance Index, Heat Removal System | 3Q/06 | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 |
UAI (ΔCDF) | -1.90E-08 | -2.00E-08 | -2.30E-08 | -2.20E-08 | -2.20E-08 | -2.20E-08 | -2.20E-08 | -2.20E-08 |
URI (ΔCDF) | -3.80E-08 | -4.20E-08 | -4.20E-08 | -4.20E-08 | -4.20E-08 | 1.50E-07 | 1.50E-07 | 1.50E-07 |
PLE | NO | NO | NO | NO | NO | NO | NO | NO |
Indicator value | -5.70E-08 | -6.20E-08 | -6.50E-08 | -6.40E-08 | -6.40E-08 | 1.28E-07 | 1.28E-07 | 1.28E-07 |
Licensee Comments: none
Mitigating Systems Performance Index, Residual Heat Removal System | 3Q/06 | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 |
UAI (ΔCDF) | 1.00E-08 | 8.50E-09 | 8.00E-09 | 1.00E-08 | 1.00E-08 | 1.00E-08 | 7.90E-09 | 6.50E-09 |
URI (ΔCDF) | -7.40E-09 | -7.40E-09 | -7.70E-09 | -7.50E-09 | -7.50E-09 | -7.50E-09 | -7.50E-09 | -7.50E-09 |
PLE | NO | NO | NO | NO | NO | NO | NO | NO |
Indicator value | 2.60E-09 | 1.10E-09 | 3.00E-10 | 2.50E-09 | 2.50E-09 | 2.50E-09 | 4.00E-10 | -1.00E-09 |
Licensee Comments: none
Mitigating Systems Performance Index, Cooling Water Systems | 3Q/06 | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 |
UAI (ΔCDF) | 8.60E-10 | 8.60E-10 | 9.00E-10 | 1.10E-09 | 1.90E-09 | 1.90E-09 | 1.50E-09 | -1.00E-10 |
URI (ΔCDF) | 4.30E-08 | 4.50E-08 | -2.00E-08 | -2.00E-08 | -2.00E-08 | -2.00E-08 | -1.20E-08 | -1.20E-08 |
PLE | NO | NO | NO | NO | NO | NO | NO | NO |
Indicator value | 4.39E-08 | 4.59E-08 | -1.91E-08 | -1.89E-08 | -1.81E-08 | -1.81E-08 | -1.05E-08 | -1.21E-08 |
Licensee Comments: none
Reactor Coolant System Activity | 7/06 | 8/06 | 9/06 | 10/06 | 11/06 | 12/06 | 1/07 | 2/07 | 3/07 | 4/07 | 5/07 | 6/07 |
Maximum activity | 0.000359 | 0.000386 | 0.000431 | 0.000457 | 0.000487 | 0.000540 | 0.000541 | 0.000548 | 0.000797 | 0.000183 | 0.000284 | 0.000294 |
Technical specification limit | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 |
Indicator value | 0 | 0 | 0 | 0 | 0 | 0.1 | 0.1 | 0.1 | 0.1 | 0 | 0 | 0 |
Reactor Coolant System Activity | 7/07 | 8/07 | 9/07 | 10/07 | 11/07 | 12/07 | 1/08 | 2/08 | 3/08 | 4/08 | 5/08 | 6/08 |
Maximum activity | 0.000265 | 0.000297 | 0.000322 | 0.000330 | 0.000387 | 0.000376 | 0.000424 | 0.000418 | 0.000574 | 0.000488 | 0.000489 | 0.000510 |
Technical specification limit | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 |
Indicator value | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0.1 | 0 | 0 | 0.1 |
Licensee Comments: none
Reactor Coolant System Leakage | 7/06 | 8/06 | 9/06 | 10/06 | 11/06 | 12/06 | 1/07 | 2/07 | 3/07 | 4/07 | 5/07 | 6/07 |
Maximum leakage | 0.330 | 0.520 | 0.675 | 0.571 | 0.550 | 0.269 | 0.483 | 0.477 | 0.402 | 0.157 | 0.018 | 0.019 |
Technical specification limit | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 |
Indicator value | 3.3 | 5.2 | 6.8 | 5.7 | 5.5 | 2.7 | 4.8 | 4.8 | 4.0 | 1.6 | 0.2 | 0.2 |
Reactor Coolant System Leakage | 7/07 | 8/07 | 9/07 | 10/07 | 11/07 | 12/07 | 1/08 | 2/08 | 3/08 | 4/08 | 5/08 | 6/08 |
Maximum leakage | 0.045 | 0.051 | 0.042 | 0.039 | 0.029 | 0.030 | 0.011 | 0.033 | 0.040 | 0.025 | 0.036 | 0.038 |
Technical specification limit | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 | 10.0 |
Indicator value | 0.5 | 0.5 | 0.4 | 0.4 | 0.3 | 0.3 | 0.1 | 0.3 | 0.4 | 0.3 | 0.4 | 0.4 |
Licensee Comments: none
Drill/Exercise Performance | 3Q/06 | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 |
Successful opportunities | 21.0 | 59.0 | 46.0 | 22.0 | 31.0 | 47.0 | 24.0 | 10.0 |
Total opportunities | 29.0 | 62.0 | 47.0 | 22.0 | 32.0 | 49.0 | 26.0 | 10.0 |
Indicator value | 93.9% | 94.0% | 94.7% | 94.0% | 94.2% | 93.8% | 93.7% | 93.9% |
Licensee Comments: none
ERO Drill Participation | 3Q/06 | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 |
Participating Key personnel | 154.0 | 152.0 | 155.0 | 156.0 | 156.0 | 158.0 | 159.0 | 156.0 |
Total Key personnel | 156.0 | 155.0 | 161.0 | 156.0 | 156.0 | 158.0 | 160.0 | 162.0 |
Indicator value | 98.7% | 98.1% | 96.3% | 100.0% | 100.0% | 100.0% | 99.4% | 96.3% |
Licensee Comments: none
Alert & Notification System | 3Q/06 | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 |
Successful siren-tests | 473 | 475 | 476 | 475 | 476 | 476 | 476 | 474 |
Total sirens-tests | 476 | 476 | 476 | 476 | 476 | 476 | 476 | 476 |
Indicator value | 99.4% | 99.6% | 99.6% | 99.7% | 99.9% | 99.9% | 99.9% | 99.9% |
Licensee Comments: none
Occupational Exposure Control Effectiveness | 3Q/06 | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 |
High radiation area occurrences | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Very high radiation area occurrences | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Unintended exposure occurrences | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Indicator value | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Licensee Comments: none
RETS/ODCM Radiological Effluent | 3Q/06 | 4Q/06 | 1Q/07 | 2Q/07 | 3Q/07 | 4Q/07 | 1Q/08 | 2Q/08 |
RETS/ODCM occurrences | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Indicator value | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Licensee Comments: none
Action Matrix Summary | Inspection Findings Summary | PI Summary | Reactor Oversight Process
Last Modified: August 4, 2008